Model - AP275E
Engine
Alternator

50 Hz 3- Phase Power Factor Cos ɸ = 0.8

Perkins 1306C-E87TAG6 Mecc Alte ECO38-1L/N  
Rating Prime Power (PRP) Standby Power (LTP)
Voltage kVA kWe kVA kWe Amps
380 - 415V 250 200 275 220 396

Definition of Ratings & Reference Conditions :
Prime Power (PRP) is the nominal output continuously available, where the average load (variable) does not exceed 80% of the prime power rating. 10% overload is available for a maximum of 1 hour in 12 hours of operation.

Standby Power (LTP) the maximum output available (at variable load), for up to 500 hours per year. The average load (variable) must not exceed 80% of the standby power rating. No overload is available. The genset must not operate, at standby rating, in parallel with the public utility under any circumstances. Standard Reference Conditions: air inlet temperature 25°C (77°F), barometric pressure 100kPa [110m(361ft) altitude] and 30% relative humidity.

Notes: The above ratings may be subject to derate at different operating conditions. Please see the Derate Guidelines on the Agen wesite. All power ratings and reference conditions in accordance with ISO 8528-1 and ISO 3046-1. Above ratings are for 400V, 50Hz, Cos ?=0.8

Key Features :
CE certificate
Tropical radiator
Single bearing alternator
Fully guarded engine-driven fan
Radiator matrix guard
Fully welded steel baseframe with lifting / jacking points
8 hour capacity base fuel tank
Heavy duty rubber anti-vibration mountings fitted inboard
Main line circuit breaker
Industrial exhaust silencer supplied loose
Exhaust flexible section
Spin on oil and fuel filters and dry type air filter element
24V starter batteries and connecting cables
Auto Start control system with digital instrumentation
Low oil pressure protection
High engine temperature protection
Overspeed protection
Factory Test Certificate based on ISO8528
Operation & Maintenance Manual

Overal Dimension & Weights - Open Set
Length (L) = 2540mm
Width (W) = 860mm
Height (H) = 1870mm
Weight =1920kg



Typical Open Generator Sound Pressure Level at 1m, Free Field (dB)
Overall dBA 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz
102 95 96 97 95 91
All specifications and design are subject to change without notice
Technical Specifications
Engine General Data Alternator Technical Data
Manufacturer : Perkins
Country of manufacture : United Kingdom
Model : 1306C-E87TAG6
Number of cyclinders : 6
Clylinder arrangement : Verdical in-line
Cycle : 4 stroke
Induction system : Turbocharged air to air aftercooled
Combustion system : Direct injection
Cooling system : Water cooled
Engine speed : 1500 rpm
Gross Engine Power : 246 kWm
Bore and stroke : 116.6mm x 135.9mm
Displacement : 8.7 litres
Compression ratio : 16.9:1
Total lubrication capacity : 26.4 litres
Total coolant capacity : 37.2 litres

Fuel Consumption
Engine Speed 1500 rev/min 1800 rev/min
g/kWh l/hr g/kWh l/hr
Standby 63,3
Prime power 58,9
Continuous baseload
75% of prime power 46,1
50% of prime power 31,1
25% of prime power
Manufacturer : Meccalte
Country of manufacture : United Kingdom
Model : ECO38-1L/N
Number of bearing : 1
Insulation class : H
Winding pitch : 2/3
Winding leads : 12
Protection : IP23
Excitation system : Self - excited *
AVR model : SR7/2**
Maximum overspeed : 2250 rev/min
Voltage regulation : ± 1.0 %
External voltage adjustment : ± 5 %
Radio interference : VDE 0875 degree K

* The self-regulation is obtained through an electronic regulator. The regulator is fed by an auxiliary winding which guarantees an almost constant supply under any possible operating condition of the generator.
** This regulator is equipped with a low speed and overload protection with an adjustable intervention threshold, it works at 50/60 Hz, it has adjustable voltage stability and it offers the possibility for a remote voltage regulation.


Control Module Specification
Auto Mains Failure Control Module DSE7220

Automatic load transfer
USB connectivity
132 x 64 pixcel LCD display
Event logging (30) showing date and time
Fully configurable via PC software
LED and LCD alarm indication
Engine execise mode
kWh monitoring
Configurable timers and alarms
Backed up real time clock
Multiple date and time maintenance scheduler
Robust module enclosure
Front panel editor
Five key menu navigation
Nine configurable inputs
Six configurable outputs
Power save mode

Instrumentation
Generator Volts L1-N, L2-N, L3-N
Generator Volts L1-L2, L2-L3, L3-L1
Generator Amps L1,L2,L3
Generator Frequency Hz
Engine speed RPM
Engine Oil Pressure
Fuel Level %
Engine Temperature
Battery Volts
Engine Hours Run
Generator kVA
Generator kW
Generator Power Factor
Mains Volts L1-N, L2-N, L3-N
Mains Volts L1-L2, L2-L3, L3-L1
Mains Frequency Hz
Generator Power Factor
Charge Alternator Voltage
Generator kVAr
Generator kWh, kVAh, kVArh
Number of engine start


Home Page | About Us | Services | References | Contact