Engine
|
Alternator
|
50 Hz 3- Phase Power Factor Cos ɸ = 0.8
|
Perkins 4008TAG1A |
Newage Stamford HCI 634H |
|
|
Rating |
Prime Power (PRP) |
Standby Power (LTP) |
Voltage |
kVA |
kWe |
kVA |
kWe |
Amps |
415/240 |
900 |
720 |
1000 |
800 |
1391 |
400/230 |
900 |
720 |
1000 |
800 |
1443 |
380/220 |
900 |
720 |
1000 |
800 |
1519 |
|
Definition of Ratings & Reference Conditions :
Prime Power (PRP) is the nominal output continuously available, where the average load (variable) does not exceed 80% of the prime
power rating. 10% overload is available for a maximum of 1 hour in 12 hours of operation.
Standby Power (LTP) the maximum output available (at variable load), for up to 500 hours per year. The average load (variable) must not
exceed 80% of the standby power rating. No overload is available. The genset must not operate, at standby rating, in parallel with the
public utility under any circumstances.
Standard Reference Conditions: air inlet temperature 25°C (77°F), barometric pressure 100kPa [110m(361ft) altitude] and 30% relative humidity.
Notes: The above ratings may be subject to derate at different operating conditions. Please see the Derate Guidelines on the Agen wesite.
All power ratings and reference conditions in accordance with ISO 8528-1 and ISO 3046-1.
|
Key Features :
CE certificate
Tropical radiator
Single bearing Stamford alternator with PMG
Fully guarded engine-driven fan
Radiator matrix guard
Fully welded steel baseframe with lifting / jacking points
8 hour capacity base fuel tank
Heavy duty rubber anti-vibration mountings fitted inboard
Main line circuit breaker (optional)
Industrial exhaust silencer supplied loose
Exhaust flexible section
Jacket water heater
Constant potential battery charger
24V starter batteries and connecting cables
Auto Start control system with digital instrumentation
RS232/RS485
Low oil pressure protection
High engine temperature protection
Overspeed protection
Low coolant level protection
Factory Test Certificate based on ISO8528
Operation & Maintenance Manual
|
Overal Dimension & Weights - Open Set
Length (L) = 4650mm
Width (W) = 2050mm
Height (H) = 2270mm
Dry Weight = 7500kg
Wet Weight = 7740kg
|
Typical Open Generator Sound Pressure Level at 1m, Free Field (dB)
Overall dBA |
250 Hz |
500 Hz |
1000 Hz |
2000 Hz |
4000 Hz |
111 |
105 |
105 |
105 |
104 |
101 |
All specifications and design are subject to change without notice
|
Technical Specifications
Engine General Data |
Alternator Technical Data |
Manufacturer |
: Perkins |
Country of manufacture |
: United Kingdom |
Model |
: 4008TAG1A |
Number of cyclinders |
: 8 |
Clylinder arrangement |
: Verdical in-line |
Cycle |
: 4 stroke |
Induction system |
: Turbocharged air to air aftercooled |
Combustion system |
: Direct injection |
Cooling system |
: Water cooled |
Engine speed |
: 1500 rpm |
Gross Engine Power |
: 882 kWm |
Bore and stroke |
: 160mm x 190mm |
Displacement |
: 30.561 litres |
Compression ratio |
: 13.6:1 |
Total lubrication capacity |
: 153 litres |
Total coolant capacity |
: 149 litres |
Fuel Consumption |
Engine Speed |
1500 rev/min |
1800 rev/min |
g/kWh |
l/hr |
g/kWh |
l/hr |
Standby |
210 |
218 |
|
|
Prime power |
206 |
195 |
|
|
Continuous baseload |
|
|
|
|
75% of prime power |
201 |
143 |
|
|
50% of prime power |
207 |
98 |
|
|
25% of prime power |
217 |
52 |
|
|
|
|
Manufacturer |
: Stamford |
Country of manufacture |
: United Kingdom |
Model |
: HCI 634H |
Number of bearing |
: 1 |
Insulation class |
: H |
Winding pitch |
: 2/3 |
Winding leads |
: 6 |
Protection |
: IP23 |
Excitation system |
: Seperately excited by P.M.G. * |
AVR model |
:
MX321
|
Maximum overspeed |
: 2250 rev/min |
Voltage regulation |
: ± 0.5 % |
External voltage adjustment |
: ± 10 % |
Telephone interference |
: THF<2% |
* This sophisticated Automatic Voltage Regulator (AVR) is incorporated into the Stamford Permanent Magnet Generator (PMG) system and is fitted as standard to generator of this type.
MX321 is a three phase sensed Automatic Voltage Regulator and forms part of the excitation system for a brush-less generator. Excitation power is derived from a three-phase PMG, to solate the AVR control circuits from the effects of non-lineer loads and reduce radio frequency interference on the generator terminals. Sustained generator short circuit current is another feature of the PMG system. Three phase RMS sensing is employed for superior voltage regulation.
|
|
Control Module Specification
|
Auto Mains Failure Control Module DSE7220
Automatic load transfer
USB connectivity
132 x 64 pixcel LCD display
Event logging (30) showing date and time
Fully configurable via PC software
LED and LCD alarm indication
Engine execise mode
kWh monitoring
Configurable timers and alarms
Backed up real time clock
Multiple date and time maintenance scheduler
Robust module enclosure
Front panel editor
Five key menu navigation
Nine configurable inputs
Six configurable outputs
Power save mode
|
Instrumentation
Generator Volts L1-N, L2-N, L3-N
Generator Volts L1-L2, L2-L3, L3-L1
Generator Amps L1,L2,L3
Generator Frequency Hz
Engine speed RPM
Engine Oil Pressure
Fuel Level %
Engine Temperature
Battery Volts
Engine Hours Run
Generator kVA
Generator kW
Generator Power Factor
Mains Volts L1-N, L2-N, L3-N
Mains Volts L1-L2, L2-L3, L3-L1
Mains Frequency Hz
Generator Power Factor
Charge Alternator Voltage
Generator kVAr
Generator kWh, kVAh, kVArh
Number of engine start
|
|