Engine
|
Alternator
|
50 Hz 3- Phase Power Factor Cos ɸ = 0.8
|
Perkins 1006TG2A |
Mecc Alte ECP34-2S |
|
|
Rating |
Prime Power (PRP) |
Standby Power (LTP) |
Voltage |
kVA |
kWe |
kVA |
kWe |
Amps |
380 - 415V |
105 |
84 |
115 |
92 |
166 |
|
Definition of Ratings & Reference Conditions :
Prime Power (PRP) is the nominal output continuously available, where the average load (variable) does not exceed 80% of the prime
power rating. 10% overload is available for a maximum of 1 hour in 12 hours of operation.
Standby Power (LTP) the maximum output available (at variable load), for up to 500 hours per year. The average load (variable) must not
exceed 80% of the standby power rating. No overload is available. The genset must not operate, at standby rating, in parallel with the
public utility under any circumstances.
Standard Reference Conditions: air inlet temperature 25°C (77°F), barometric pressure 100kPa [110m(361ft) altitude] and 30% relative humidity.
Notes: The above ratings may be subject to derate at different operating conditions. Please see the Derate Guidelines on the Agen wesite.
All power ratings and reference conditions in accordance with ISO 8528-1 and ISO 3046-1.
Above ratings are for 400V, 50Hz, Cos ?=0.8
|
Key Features :
CE certificate
Tropical radiator
Single bearing alternator
Fully guarded engine-driven fan
Radiator matrix guard
Fully welded steel baseframe with lifting / jacking points
8 hour capacity base fuel tank
Heavy duty rubber anti-vibration mountings fitted inboard
Main line circuit breaker
Industrial exhaust silencer supplied loose
Exhaust flexible section
Spin on oil and fuel filters and dry type air filter element
12V starter batteries and connecting cables
Auto Start control system with digital instrumentation
Low oil pressure protection
High engine temperature protection
Overspeed protection
Factory Test Certificate based on ISO8528
Operation & Maintenance Manual
|
Overal Dimension & Weights - Open Set
Length (L) = 2110mm
Width (W) = 730mm
Height (H) = 1490mm
Weight =1250kg
|
Typical Open Generator Sound Pressure Level at 1m, Free Field (dB)
Overall dBA |
250 Hz |
500 Hz |
1000 Hz |
2000 Hz |
4000 Hz |
98 |
90 |
92 |
93 |
93 |
86 |
All specifications and design are subject to change without notice
|
Technical Specifications
Engine General Data |
Alternator Technical Data |
Manufacturer |
: Perkins |
Country of manufacture |
: United Kingdom |
Model |
: 1006TG2A |
Number of cyclinders |
: 6 |
Clylinder arrangement |
: Verdical in-line |
Cycle |
: 4 stroke |
Induction system |
: Turbocharged |
Combustion system |
: Direct injection |
Cooling system |
: Water cooled |
Engine speed |
: 1500 rpm |
Gross Engine Power |
: 105 kWm |
Bore and stroke |
: 100mm x 127 mm |
Displacement |
: 5.99 litres |
Compression ratio |
: 16.0:1 |
Total lubrication capacity |
: 16.1 |
Total coolant capacity |
: 27.7 litres |
Fuel Consumption |
Engine Speed |
1500 rev/min |
1800 rev/min |
g/kWh |
l/hr |
g/kWh |
l/hr |
Standby |
|
24,1 |
|
28,4 |
Prime power |
|
21,8 |
|
25,8 |
Continuous baseload |
|
|
|
|
75% of prime power |
|
16,5 |
|
19,9 |
50% of prime power |
|
11,4 |
|
14 |
25% of prime power |
|
|
|
|
|
|
Manufacturer |
: Meccalte |
Country of manufacture |
: United Kingdom |
Model |
: ECP34-2S |
Number of bearing |
: 1 |
Insulation class |
: H |
Winding pitch |
: 2/3 |
Winding leads |
: 12 |
Protection |
: IP23 |
Excitation system |
: Self - excited * |
AVR model |
: SR7/2** |
Maximum overspeed |
: 2250 rev/min |
Voltage regulation |
: ± 1.0 % |
External voltage adjustment |
: ± 5 % |
Radio interference |
: VDE 0875 degree K |
* The self-regulation is obtained through an electronic regulator. The regulator is fed by an auxiliary winding which guarantees an almost constant supply under any possible operating condition of the generator.
** This regulator is equipped with a low speed and overload protection with an adjustable intervention threshold, it works at 50/60 Hz, it has adjustable voltage stability and it offers the possibility for a remote voltage regulation.
|
|
Control Module Specification
|
Automatic Engine Control Module DSE521K
The Model 521 is an Automatic Engine Control Module designed to automatically start and stop the engine.
It will indicate the operational status and fault conditions, automatically shut down the engine and indicate the engine failure by a flashing LED on the front panel.
Other simultaneous faults are indicated by steady LED.
Operation of the module is via a three position rotary key-switch mounted on the front panel with STOP, AUTO and MANUAL positions.
Remote PC-controlled engine starting and stopping is also featured.
Configurable inputs available for:
* Low Oil Pressure
* High Engine Temperature
* Remote Start.
|
Alarms & Instrumentations
Multiple alarm channels are provided to monitor the following:
Under/Overspeed
Charge Fail
Emergency Stop
Low oil pressure
High engine temperature
Fail to Start
Fail to stop
Loss of speed sensing
Analogue instrumentations for monitoring are:
Generator ammeters
Generator voltmeter
Voltmeter selector switch
Frequency/rpm indication
Hourcounter
Battery charger on/off pushbutton
Engine oil pressure
Engine water temperature
Battery voltmeter
Emergency Stop
|
|